Product Structure
Sinopak MVVFD includes integrated structure and split-type structure based on capacity. The integrated structure is adopted in low capacity MV VFD and the split-type structure is adopted in high capacity MV VFD. In terms of an integrated machine, which is compact in size, phase-transformer, power units, control systems, and power frequency bypass are fully integrated into one cabinet; In terms of a split-type machine, phase-transformer, power units, control systems and power frequency bypass are assembled in separate cabinets in which are combined on the spot.
Medium voltage input
3KV, 3.3KV, 4.16KV, 6KV, 6.6KV, 10KV, 11KV (-20%~+15%)
50/60 Hz¡À10%
Medium voltage output
0~Rated voltage
0~50/60 Hz, 0.01 Hz
Multilevel PWM sin wave, total harmonic distortion (THD) < 4%
Performance
Inversion efficiency at an rated load > 98.5%,
overall efficiency (including the transformer) > 97%
Power factor (within the range of speed regulation) > 0.95,
power factor (at a rated load) > 0.97
Overload capacity: 110%: long-term stable operation, 120%: 1 minute, 150%: 2 seconds, and 160%: prompt protection
Allowable outage duration: 200 ms (and longer under light load)
Mean time between failures: > 100,000 hours
Control mode: flux optimization and control with space vector PWM
Acceleration/deceleration time: 1 to 3,600 seconds
Switching quantity input/output:11-way/10-way
Analog input: 4-way (optional: 0 to 5 V, 4 to 20 mA)
Analog output: 3-way (optional: 0 to 10 V, 4 to 20 mA )
Communications: RS485 interface, Modbus-based (optional Profibus-DP and Ethernet interfaces)
Control power supply: Single-phase 220 V AC, 5kVA
Excitation control ( dedicated for the synchronous motor)
Automatic excitation control, manual excitation control, multi-stage speed excitation control, and external excitation control for the MVVFD
Environment: Operating in indoor environment without explosive or corrosive gases, conductive dust, or oil fog
Operating ambient temperature: 0 degree~+45 degree
Storage and transportation temperature: -40 degree ~+70 degree
Ambient humidity: < 90% (No condensation)
Operating altitude: Derating required for an altitude greater than 1000 meters
Protection function: Overcurrent, overload, short circuit, three phase current unbalance, immediate electric outage, input/output phase loss, overvoltage, undervoltage, body overheat, transformer overheat, shutdown due to external fault, and power unit auto bypass
Cooling mode: Forced-air cooling
User interface: An 10-inch Human Machine Interface
Protection grade: IP31